MODELS 106-PR-48/206-PR-48

PRESSURE REDUCING VALVE WITH LOW FLOW BY-PASS

KEY FEATURES

  • Maintains stable flow right down to zero
  • Precise and reliable pressure setting
  • By-pass piped in parallel to reduce space requirements

How May We Assist You?

*
*
*
*

  1. PRODUCT OVERVIEW

    106/206-PR-48 Pressure Reducing Valve with Low Flow By-Pass

    The pilot valve senses the downstream pressure through a connection at the main valve outlet. Under flowing conditions, the pilot reacts to small changes in pressure to control the main valve position by modulating the pressure above the diaphragm. The downstream pressure is maintained relatively steady at the pilot set-point.

    The by-pass valve is set 5 psi / 0.35 bar higher than the main valve. Under low flow conditions, the main PR valve closes and the by-pass stays open, controlling the pressure at very low flows without seat chatter.

    In typical pressure reducing applications, the reduced port Model 206-PR-48 is often the best selection.

  2. DOWNLOADS

    106/206-PR-48 Pressure Reducing Valve with Low Flow By-Pass

    For more information on the 106 / 206-PR-48 pressure reducing valve:

    Download the 106/206 PR-48 Product Guide

    Download the 106/206-PR-48 Operation Guide